  • Counterclockwise rotation for VETEC series 72, 73, 82 (counterclockwise closing) - Rotary angle 75°.
  • Clockwise rotation for VETEC series 62 (clockwise closing) - Rotary angle 90°.

Techical data

Application   Control and on/off application
Sizes   60 to 10000
Design Type AT (SC/SO) Double-acting piston; single-acting with spring return; encapsulated spring assemblies
  Type AT (DL) Double-acting piston; double-acting without spring return; without spring assemblies
Other versions   For low temperatures; quick-closing; made of stainless steel
Actuator movement   Rotary
Left-turning for series 72, 73, 82 (counterclockwise closing)
Right-turning for series 62 (clockwise closing)
Rotary angle   0 to 75° for series 72, 73, 82
0 to 90° for series 62
Power supply   Pneumatic
Control air range   3 to 6 bar
Safety function Type AT (SC/SO) Spring force closes (FC): Actuator type SC
Spring force opens (FO): Actuator type SO
  Type AT (DL) Without
Torques Type AT (SC/SO) 13 to 4068 Nm
  Type AT (DL) 35 to 10007 Nm
Permissible ambient temperature   -40 to +80 °C
-55 to + 80 °C (version for low temperature)
Differential pressures for actuator sizing   TY005.069
Rotating angle limitation (optional)   Internal or external stroke limitation (end stops)
Interface to valve   according to DIN EN ISO 5211
Interface for attachments   In accordance with VDI/VDE 3845-1 (EN 15714-3) or VDI/VDE 3847-2 (IPM attachment kit)
Conformity   EAC
Modulating duty (without manual override)

Actuator

 

Modulating and manual operation (for actuators with manual override)

Actuator with manual gearbox

 

Mounting kits (attachment kits)

Mounting kit with connections according to DIN EN ISO 5211
Mounting kits Actuator with manual gear boxes

Mounting arrangements (mounting positions of the actuator) and mounting positions

Mounting arrangements

Mounting types A, B*, C and D* are possible for mounting the Type AT Actuator on the valve.
* For control valves with manual gearboxes, mounting positions B and D must be checked due to the risk of collision with the pipeline.


Mounting type A is selected as the standard mounting position if no other information is available.

Exemplary illustration of mounting position A. For other mounting positions, see data sheet.

Translated with www.DeepL.com/Translator (free version) TY005.006.

Actuator
Actuator with manual gearbox

FTO = Medium opens ( flow from the front, on the seat side) • FTC = Medium closes ( flow from the rear)

 

Mounting Orientations

Control valves with AT actuators can be operated in any mounting position.


Standard mounting position: horizontal pipeline.

FTO = Medium opens • FTC = Medium closes

Accessories

The control valves can be equipped with various accessories: Positioner, solenoid valve, supply pressure regulator, limit switch, volume booster/booster and other attachments.

 

Mounting of accessories (attachments) to pneumatic rotary actuators is performed according to two standardized mounting methods:

VDI/VDE 3845-1 (EN 15714-3)

Mounting of the accessories with air connections - Piping

 

Direct attachment according to VDI/VDE 3847-2 (IPM attachment kit)

Modular design with integrated air ducting and a direct air connection, without additional piping. Customer-oriented solution.

 

Certificates and manufacturer's declarations

EU/CE conformity

Conformity declaration
ATX-ISTR09 (Air Torque)
RL 2014/34/EU (ATEX) Excluded from the scope according to ignition hazard assessment according to DIN EN 13463-1:2001, para. 5.2
Conformity declaration
ATEU-2019 (Air Torque)
RL 2014/68/EU (DGRL) Excluded from the scope of Art. 1, § 2, letter j)
Conformity declaration
ATEU-2019 (Air Torque)
RL 2006/42/EG (MRL) Incomplete machine (valve actuator with or without interface according to EN ISO 5211)

Safety integrity level (SIL)

Certificate
968/V 1054.01/18 (Air Torque)
IEC 61508 Applicable up to SIL 2 and with redundant instrumentation up to SIL 3

TR CU (EAC)

Certificate
RU C-IT.MX24.B.00428 (Air Torque)
TP TC 010/2011 (EAC)
(TR CU)
Safety of machinery MRL (RU, BLR, KAZ)
Certificate
RU C-IT. ГБ 08.B.01646 (Air Torque)
TP TC 012/2011 (EAC/Ex)
(TR CU)